Pentair MASTERTEMP 250K BTU/HR User Manual

Browse online or download User Manual for Water equipment Pentair MASTERTEMP 250K BTU/HR. Pentair MASTERTEMP 250K BTU/HR Manuel d'utilisation [en] [ru] [de] [fr] [it] [cs] [pl] [es]

  • Download
  • Add to my manuals
  • Print
  • Page
    / 76
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
POOL AND SPA HEATER
120/240 VAC NATURAL
GAS/LP GAS
INSTALLATION
and
USER’S GUIDE
MODELS Natural Propane
200K BTU/HR 460730 460731
250K BTU/HR 460732 460733
300K BTU/HR 460734 460735
400K BTU/HR 460736 460737
IMPORTANT SAFETY INSTRUCTIONS
READ AND FOLLOW ALL INSTRUCTIONS
SAVE THESE INSTRUCTIONS
If the information in these instructions is not followed exactly, a fire
or explosion may result causing property damage, personal injury or death.
Call (800) 831-7133 for additional free copies of these instructions.
FOR YOUR SAFETY
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or
any other appliance.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electrical switch; do not use any phone in your building.
Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s
instructions.
If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency or the gas
supplier.
SPECIAL INSTRUCTIONS TO OWNER
Retain this manual for future reference.
This manual supplies information for the installation, operation,
and servicing of the appliance. READ AND REVIEW THIS
MANUAL COMPLETELY before proceeding with an installation.
Its use will reduce service calls and chance of injury and will
lengthen product life.
CERTIFIED
®
®
MasterTemp
TM
WARNING
472592 Rev. A (04/04/06)
Page view 0
1 2 3 4 5 6 ... 75 76

Summary of Contents

Page 1 - MasterTemp

POOL AND SPA HEATER120/240 VAC NATURALGAS/LP GAS INSTALLATIONandUSER’S GUIDEMODELS Natural Propane200K BTU/HR 460730 460731250K BTU/HR 46073

Page 2 - AND SERVICE MANUAL

CONTROL PANEL INDEXINGThe exhaust discharges vertically from outside the ventcover. The heater control panel assembly located on thetop panel can be r

Page 3 - Continued)

NOTICE: Combustion air contaminated by corrosive chemical fumes can damage the heater and will void thewarranty (See Table 1 below).HEATER CLEARANCES

Page 4 - INSTRUCTIONS

OUTSIDE VENT COVER REMOVALThe heater is supplied from the factory with a built-instackless outside vent for outdoor installation. Removethe outside ve

Page 5 - OPERATING INSTRUCTIONS

5. Use Listed firestop for floor and ceiling penetrations.Use Listed thimble for wall penetrations. Use a Listedroof flashing, roof jack, or roof thim

Page 6 - OPERATING CONTROL

Risk of fire or asphyxiation if vent is notassembled according to manufacturer’s instructions or ifvent parts from different manufacturers are mixed.

Page 7 - AFTER START-UP

The terminal must be located (Canada):• at least 10 feet (3.3M) from any opening into a build-ing.• at least 12" (.3M) above finished grade or th

Page 8 - CARE AND MAINTENANCE

Install a check valve to prevent back-siphoning throughthe heater when the pump is off. NOTICE: Improper operation of chemical feeders cancause severe

Page 9 - HEATER CLEARANCES – OUTDOOR

17Verify proper operation of the water pressure switch atthe start of every season and every six months thereafterby the following steps:1. Lower the

Page 10 - INSTALLATION INSTRUCTIONS

18PRESSURE RELIEF VALVECanadian code requires and some U.S. local codes mayrequire installation of a pressure relief valve. Purchaseseparately and ins

Page 11 - All Air From All Air From

19Risk of fire and explosion. Improperinstallation, adjustment, alteration, service, or main-tenance of the Combination Gas Control Valve canlead to f

Page 12 - (See Figures 11 and 12)

INSTALLATION, OPERATION AND SERVICE MANUALTO INSTALLER:Affix these instructions adjacent to theheater.TO CONSUMER:Retain these instructions for future

Page 13 - Min. 10 Ft. (3.3 M)

20GAS CONNECTIONSThe heater requires a gas supply of not less than 4" (10.2cm) wc and not more than 14" (35.6cm) wc. Gas supply pressures ou

Page 14 - Roof Pitch – U.S

Connect the L1 of the power supply to the black wire,the L2 or neutral lead to the red wire, and the groundwire to the green wire.A time clock control

Page 15 - Final Installation Check

226. Reinstall the access door panels.The fuse for the Fireman’s Switch is a 1.25 amp1-1/4x1/4" fast blow fuse, available locally.MAXIMUM TEMPERA

Page 16 - Switch Settings

23Hazardous voltage. Can shock, burn or kill.Disconnect power before servicing any components.Fire and Explosion hazard. Do not jumperswitch terminals

Page 17

24Heater Will Not Fire - AStartGO TO“HEATER WILL NOT FIRE - B”Page 25Heater should fire on demandfor heat.Check Fireman’s Switch circuitconnections (t

Page 18 - PRESSURE RELIEF VALVE

25Heater Will Not Fire - BStartIncrease POOL/SPA tempera-ture setting on MembranePad above actual water tem-perature. Heater should fireon demand for

Page 19

26Heater Will Not Fire - CStartGo to “INITIALTROUBLESHOOTING”Continue to observe heaterfor several minutes. Cycleheater on and off severaltimes. Obser

Page 20 - AT LEAST 4"

27Heater Will Not Fire - DStartIMPORTANT! READ ME FIRST!!If your heater is correctly connected to 240 Volts AC, TheIgnition Control Module (ICM) will

Page 21 - Pull down to

28Diagnostic LED’s: AGS, AFS, HLS, PS, THERMISTORDo not jumper a safety switch to remedy a failed switch.NOTE: ES1 is a spare and should be jumpered.C

Page 22

29Diagnostic LED’s: SFSNO (HD )NO (Basic)NOReset power to Heater andretry. Heater should fire.Does the DigitalTemperature Display showError Code “E05”

Page 23 - Initial Troubleshooting

SAFETY INSTRUCTIONS (Continued)This appliance is equipped with anunconventional gas control valve that is factoryset with a manifold pressure of -.2 i

Page 24 - Heater Will Not Fire - A

30Burner TroubleshootingSYMPTOM CAUSE REMEDYLoud, high-pitched whine Flame is too rich. Verify pressure tap between gas valveand blower inlet.Turn to

Page 25 - Model Flow

31Repair Parts are available from your Pentair dealer.If your dealer cannot supply you, call Customer Support at 1-800-831-7133.For completeElectrical

Page 26 - Heater Will Not Fire - C

32For Heater mountingbolts and clamps, purchase separatelyBolt Down Bracket Kit, Part No. 460738.12716102856726251312118232341059

Page 27 - Heater Will Not Fire - D

33REPAIR PARTS – BURNER SYSTEMModelKey Part 200NA 250NA 300NA 400NANo.

Page 28 - THERMISTOR “on”

34REPAIR PARTS – WATER SYSTEM13202122458912111027619141513181716* Not available separately.• Not illustrated.ModelKey Part 200NA 250NA 300NA 400NANo.

Page 29 - Diagnostic LED’s: SFS

35REPAIR PARTS – ELECTRICAL SYSTEM389101112451913181542717ModelKey Part 200NA 250NA 300NA 400NANo. Description Qty. 200LP 250LP 300LP 400LP2 Heater Di

Page 30 - Burner Troubleshooting

36Pool Heater Wiring Connection DiagramPlug –12 pin120V – Black240V – RedJMP91J6JMP1JMP1External Control Interface Circuit Disabled, Heater Membrane P

Page 31

37Pool Heater Electrical Schematic Ladder DiagramL1 L2120/240 VAC120/240VACIGNITERL1S1 S2 L2F1F2 BLOWERGNDGNDCLASS IITRANSFORMER24 VAC24 VAC24VOPERATI

Page 32

© 2006 Pentair Water Pool and Spa, Inc. All rights reserved This document is subject to change without notice1620 Hawkins Ave., Sanford, NC 27330 • (9

Page 33 - REPAIR PARTS – BURNER SYSTEM

CHAUFFE-PISCINE/SPA C.A.120/240 VOLTS AU GAZ NATUREL/GPLNOTICE D’UTILISATIONINSTALLATION, FONCTIONNEMENT ET PIÈCESMODÈLES Naturel Propane200K BTU/h 4

Page 34 - REPAIR PARTS – WATER SYSTEM

The heater may not be installed within five feet of theinside surface of a pool or spa unless it is separated by asolid fence, wall or other permanent

Page 35

NOTICE D'UTILISATION, DE FONCTIONNEMENT ET D'ENTRETIENChauffe-piscine/spa au gaz modèles SR INSTALLATEUR :Ces instructions doivent être gard

Page 36 - CONNECTION DIAGRAM

INSTRUCTIONS CONCERNANT LA SÉCURITÉ (suite)Cet appareil est équipé d'une soupape àgaz non conventionnelle qui a été réglée à l'usine à unepr

Page 37

Ce chauffe-piscine/spa doit être installé à au moins cinq piedsde la paroi intérieure d'une piscine ou d'un spa, si une clôture,un mur ou to

Page 38 - SAVE THESE INSTRUCTIONS

C. N’ouvrir et ne fermer la commande du gaz qu’à la main. Nejamais utiliser d’outils. Si le réglage MARCHE-ARRÊT ne peutpas être modifié à la main, ne

Page 39

7. Attendre cinq (5) minutes pour que tout le gaz soit évacué.Si on sent une odeur de gaz, ARRÊTER! Suivre les instruc-tions «B» figurant sous «Avant

Page 40 - LA SÉCURITÉ

Le témoin HEATING (CHAUFFAGE) s'allume et reste allumé pendant que le brûleur fonctionne. Il clignote si l'eau duchauffe-piscine/spa doit êt

Page 41 - GÉNÉRALES

ENTRETIENINSTRUCTIONS D'ENTRETIENLes vapeurs inflammables risquent de causer un incendie ou une explosion. Ne pas entreposer d'essence, deli

Page 42 - ORDRE DE FONCTIONNEMENT

INSTRUCTIONS CONCERNANTLES INSTALLATIONS EXTÉRIEURESChauffe-piscine/spa installés à l'extérieur et utilisant le systèmed'évacuation des gaz

Page 43 - TEMPÉRATURE DES SPAS

INDEXAGE DU BLOC DE COMMANDELes gaz brûlés sont refoulés verticalement par l'extérieur du couvercle d'évacuation.Le bloc de commande du chau

Page 44 - AVERTISSEMENT

CHAUFFE-PISCINES/SPAS INSTALLÉS ÀL'EXTÉRIEUR DANS UN ABRILes dégagements suivants doivent être respectés avec toutesles surfaces combustibles :Au

Page 45 - APRÈS LA MISE EN MARCHE

C. Use only your hand to turn the gas control on or off.Never use tools. If you cannot change the ON/OFFsetting by hand, don’t try to repair it, call

Page 46 - ENTRETIEN

DÉPOSE DU COUVERCLE EXTÉRIEUR DU CONDUIT DES GAZ BRÛLÉSPour les installations extérieures, le chauffe-piscine/spa est livréavec une évacuation extérie

Page 47

gaz brûlés installés à l'horizontale doit être d'au moins 1/4de pouce par pied (2 cm par mètre) à partir du chauffe-piscine/spa. Installer u

Page 48

Risque d'incendie ou d'asphyxie si le conduitd'évacuation des gaz brûlés n'est pas assemblé conformément au mode d'emploi du

Page 49

Le mitre du conduit doit être positionné (Canada):• à au moins 10 pieds (3,30 mètres) de toute ouverture d'unbâtiment.• à au moins 12 pouces (0,3

Page 50

S'assurer que la tuyauterie de refoulement du chauffe-piscine/spa ne comporte aucune vanne ou obstruction du débitqui risquerait d'empêcher

Page 51

174. Attendre une minute. Le témoin «Service System» doit s'allumer, mais le brûleur ne doit pas s'allumer et la soufflante ne doit pas déma

Page 52

18SOUPAPE DE SÛRETÉLe code canadien exige et, aux États-Unis certains codes desmunicipalités peuvent l’exiger, l’installation d’une soupape desûreté.

Page 53

19Risque d'incendie et d'explosion. Toutemauvaise installation, tout mauvais réglage, toute trans-formation, tout mauvais entretien de la so

Page 54 - MANOSTAT

20BRANCHEMENTS DU GAZL'arrivée du gaz au chauffe-piscine/spa doit être d'au moins 4pouces (10,2cm) à la colonne d'eau et ne pas dépasse

Page 55

7. Ne pas brancher d'interrupteurs unipolaires, y compris desdispositifs de protection, sur le câble de mise à la terre. Lechauffe-piscine/spa n’

Page 56

8. Push the toggle switch away from you to switch thegas on.9. Replace the Door Access Panels. All panels must bein place when operating the heater.10

Page 57

226. Reposer les moitiés les panneaux de la porte d'accès.Le fusible de l'interrupteur de coupure pompier est un fusiblede 1,25 ampère de 1

Page 58

23Tension dangereuse. Risque de secousse électrique, de brûlures, voire de mort. Couper le courant avant d'intervenir sur un élément.Risque d&apo

Page 59 - COUPURE POMPIER

24Le chauffe-piscine/spa ne s'allume pas - ADébutSE REPORTER À « LE CHAUFFE-PISCINE/SPA NES’ALLUME PAS - B », page 25.Le chauffe-piscine/spa doit

Page 60

25Le chauffe-piscine/spa ne s'allume pas - BDébutAugmenter le réglage de la tempéra-ture du CHAUFFE-PISCINE/SPAavec le clavier à membrane par rap

Page 61 - AVERTISSEMENTAVERTISSEMENT

26Le chauffe-piscine/spa ne s'allume pas - CDébutPasser à «RECHERCHES INITIALESDES PANNES»Continuer d'observer le chauffe-piscine/spa pendan

Page 62

27Le chauffe-piscine/spa ne s'allume pas - DDébutIMPORTANT! - À LIRE EN PREMIER!!Si le chauffe-piscine/spa est bien relié au courant alternatif d

Page 63

28DEL de diagnostic : AGS, AFS, HLS, PS et THERMISTANCENe pas contourner un contacteur de sécuritépour remédier à un contacteur défectueux.NOTA : ES1

Page 64

29DEL de diagnostic : SFSNO (HD )NON (De base)NONRétablir le courant alimentant lechauffe-piscine/spa et réessayer.Il doit s’allumer.Est-ce que l’affi

Page 65

30Recherche des pannes du brűleurSYMPTÔMES CAUSES REMÈDESFort bruit aigu de gémissement La flamme est trop riche. Vérifier la prise de pression, entre

Page 66

31On peut se procurer des pièces de rechange auprès du concessionnaire Pentair.Si votre concessionnaire ne peut pas fournir ce dont vous avez besoin,

Page 67

The SERVICE SYSTEM light indicates that there isinsufficient water flow to the heater. If the pump is oper-ating, this usually indicates that the filt

Page 68 - SYMPTÔMES CAUSES REMÈDES

322716102885672625131211923234Pour les vis et les colliersde fixation du chauffe-piscine/spa, acheterséparément le nécessairede upport de fixation,n°

Page 69

33PIÈCES DE RECHANGE DU SYSTÈME DU BRÛLEURModèleDésignation 200NA 250NA 300NA 400NARéf. des pièces Qté 200LP 250LP 300LP 400LP1 Trousse de soupape de

Page 70

34PIÈCES DE RECHANGE DU SYSTÈME D'EAU13202122458912111027619141513181716* Pas disponibles séparément.• Pièces non illustrées.ModèlesDésignation 2

Page 71 - * Pas livrables séparément

35PIÈCES DE RECHANGE DU SYSTÈME ÉLECTRIQUE389101112451913181542717ModèlesDésignation 200NA 250NA 300NA 400NARéf. des pièces Qté 200LP 250LP 300LP 400L

Page 72 - • Pièces non illustrées

36Schéma des connexions électriques du chauffe-piscine/spaJMP91J6JMP1JMP1VALTHINDGND24VAC24VACFS1PSHLSES1AFSAGSSFSGASF1 F224VACS1240S1/120L1L1L2BMFLF1

Page 73 - Pièces non illustrées

37Diagramme en échelle du schéma électrique du chauffe-piscine/spaC. a. 120 VC. a. 120 VL1S1 S2 L2F1F2SOUFFLANTETERRETERREC. a. 24 VC. a. 24 V24VLOGIQ

Page 74 - SCHÉMA DES CONNEXIONS

Pour obtenir les données techniques du produit, communiquez avec l’installateur ouappelez au numéroSanford, North Carolina (8 A.M. to 5 P.M.)Phone: (8

Page 75 - DIAGRAMME EN ESCALIER

CARE AND MAINTENANCEMAINTENANCE INSTRUCTIONSRisk of fire or explosion from flammablevapors. Do not store gasoline, cleaning fluids, varnishes,paints,

Page 76 - PRÉSERVER CES INSTRUCTIONS

OUTDOOR INSTALLATION INSTRUCTIONSFor heaters located outdoors, using the built-in stacklessventing system.Risk of explosion if a unit burning propaneg